V6R VRF 50Hz
143
2.29 CA1, CA2, CA3, CA4, CA5: Connection combination error
Digital display output
Description
ï‚§ Connection combination error.
ï‚§ All units stop running.
ï‚§ Error code is only displayed on the master unit.
Trigger / recover condition
ï‚§ Trigger condition:
The types of inside equipment that can be connected to the V6R series heat recovery outdoor unit include:
• Standard air-cooled indoor unit (Fresh air indoor unit is treated as standard indoor unit)
• AHU KIT
• High temperature hydraulic module HT
The following connection combinations are allowed:
• VRF Indoor + AHU KIT
• VRF Indoor + HT
• VRF Indoor only
In addition to the above three cases, when the remaining connection combination is detected, the connection
combination failure is reported.
CA1
The system contains non-V6 series units (the highest priority).
CA2
Only AHU KIT.
CA3
Only HT
CA4
Only HT + AHU KIT
CA5
VRF Indoor + AHU KIT + HT
ï‚§ Recover condition:
Detected correct combination.
ï‚§ Reset method: Manually restart.
Possible causes
ï‚§ Combination does not meet the requirements.
Procedure
CA1, CA2, CA3, CA4, CA5
Change indoor unit combination

Table of Contents

Other manuals for Midea MV6-R335WV2RN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MV6-R335WV2RN1 and is the answer not in the manual?

Midea MV6-R335WV2RN1 Specifications

General IconGeneral
BrandMidea
ModelMV6-R335WV2RN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals