V6R VRF 50Hz
124
Midea
V6R
Series Service Manual
2.19 P1: High pressure protection
Digital display output
Description
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
High pressure sensor protection
Trigger condition: Discharge pressure ≥ 3.9 MPa.
Recover condition:
Cooling Only/Main Cooling Discharge pressure < 3.5MPa and Restart permission=ON.
Heating Only/Main Heating Discharge pressure < 3.1MPa and Restart permission=ON.
Reset method: Resume automatically.
Discharge pressure switch protection
Trigger condition: Discharge pressure 4.0 MPa.
Recover condition: Discharge pressure < 3.0MPa.
Possible causes
Outdoor unit stop valves are closed.
Pressure sensor/switch not connected properly or has malfunction.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Outdoor main PCB damaged.