2.9 F1: DC bus voltage error
Digital display output
Description
ï‚§ All units stop running.
ï‚§ Error code is displayed on the unit with the error.
Trigger / recover condition
ï‚§ Trigger condition: DC bus voltage < 300V or DC bus voltage >800V continuously for 10 seconds.
ï‚§ Recover condition: DC bus voltage goes back to normal.
ï‚§ Reset method: Restart automatically.
Possible causes
ï‚§ Loosened wiring of the compressor inverter module.
ï‚§ Incorrect wiring of the reactor and DC bus wire.
ï‚§ Abnormal power supply.
ï‚§ Inverter module damaged.
Procedure