MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
Troubleshooting 91
S8 definition S10 definition
reserve
reserve
ENC1 definition ENC2 definition
Outdoor unit address setting switch Effective to
0-3,
0 Stand for main unit, 1-3 Stand for slave unit
Outdoor unit capacity setting switch Effective to
9-C, 9-C Stand for 26HP~32HP
ENC3 &S12 definition
Setting the numbers of indoor unit to be 0-15
Setting the numbers of indoor unit to be 16-31
Setting the numbers of indoor unit to be 32-47
Setting the numbers of indoor unit to be 48-63
ENC4 definition
Network address setting dial switch Effective to 0-7
0-7 Stand for 0-7

Table of Contents