39
The main 5VDC is supplied on this connector. If there is no 5VDC, the relays and isolation circuits will not
operate.
J2 - Analog Input/ Output Connector
This sends and receives analog signals to and from the 9600-10 board.
J3 - Digital Input/ Output Connector
This allows the 9700-10 microcontroller board to control the relays and read the optical isolators.
J4 - Motion Connector
This connects through the Amphenol connector to the limit switches and tachometer to feed their signals to
the 9600-11 board.
J5 - Power Supply Connector
Connects through the Amphenol connector to the welding power supply and sends and receives information
to and from it.
J6 - Auxiliary Unit Connector
Connects through the Amphenol S2 connector to a second 9700 control or a PLC.
J7 - Motor Control Connector
This sends a -10VDC to +10VDC signal to the motor control module to control the speed of the motor.
J8 - Emergency Stop Condition Connector
This connection is for an emergency stop condition. It energizes a solid state relay that controls power to
the motor control.
J9 - Emergency Stop Connector
This is where the emergency stop switch is tied. If the circuit is broken, the system will disable movement.
COMPONENTS
SW1 - Remote Emergency Stop Selector Switch
In the “up” position (towards CR7), the remote emergency stop function is overridden.
In the “down” position (towards J9), the remote emergency stop function is active.
JP1-3 - Tachometer Voltage Range
Ranges are as follows:
JP1 0 to 10VDC Input Range
JP2 0 to 33VDC Input Range