FA-101T Installation and Operation Manual
11
Underwriter’s Labs Inc. (ULI) United States 2-Wire Smoke Detector
Control Panel Compatibility
Notes:
Reset time, hold for five seconds minimum.
Whether mixing different models of compatible smoke detectors, or using the same
model on the same circuit, total standby current of all detectors must not exceed 3
mA.
The below-listed smoke detectors are compatible with initiating circuits having
Compatibility Identifier "A".
Smoke
Detector
Make Model /
Base
Compatibility
Identifier
Head / Base
Rated
Standby
Current
Smoke Detector
Make Model /
Base
Compatibility
Identifier Head /
Base
Rated Standby
Current
System Sensor Sentrol - ESL
1100 A - N/A 0.12 mA 429C S10A - N/A 0.10 mA
1151/
B110LP
A - A 0.12 mA 429CT S10A - N/A 0.10 mA
1151/
B116LP
A - A 0.12 mA 429CST S11A - N/A 0.10 mA
1400 A - N/A 0.10 mA 429CRT S11A - N/A 0.10 mA
1451/B401 A - A 0.12 mA
711U/701E,
701U, 702E,
702U
S10A - S00 0.10 mA
1451/
B401B
A - A 0.12 mA
712U / 701E,
701U, 702E,
702U
S10A - S00 0.10 mA
1451/
B406B
A - A 0.12 mA
713-5U / 701E,
701U, 702E,
702U
S10A - S00 0.10 mA
1451DH/
DH400
A - A 0.12 mA
713-6U / 701E,
701U, 702E,
702U
S10A - S00 0.10 mA
2100 A - N/A 0.12 mA
721U / 702E,
702U
S10A - S00 0.10 mA
2100T A - N/A 0.12 mA
721UT / 702E,
702U
S10A - S00 0.10 mA
2151/
B110LP
A - A 0.12 mA
722U / 702E,
702U
S10A - S00 0.10 mA
2151/
B116LP
A - A 0.12 mA
731U / 702E,
702U, 702RE,
702RU
S11A - S00 0.10 mA