FA-101T Installation and Operation Manual
1
Introduction
The FA-101T is a supervised single-zone 24V DC Fire Alarm Control Panel. The panel provides the
following features:
1 Class B detection zone
1 Class B signal zone, 1.7A
DIP switch selectable signal circuit outputs such as temporal or steady
Alarm and trouble relay contacts
Remote trouble and A.C. ON indication
Zone silence/disconnect switch
Buzzer silence switch
LED indicators for zone alarm and trouble, A.C. On, Battery Fault, Ground Fault, Common
Trouble, Signal Trouble and Signal Silenced
Mechanical Installation
The panel can be surface or flush mounted. Refer to Figure 1 on page 5 for dimensions.
Surface Mounting
1. Mark the location of the four mounting holes.
2. Install the top two screws into the wall and place the panel over the screws.
3. Install the bottom screws and tighten down all four screws.
Flush Mounting
1. Make the wall cut-out according to the panel dimensions.
2. Remove the control panel door.
3. Mount the flush mounting trim (model FA-102TR) to the back box using the screws and nuts
provided with the flush mounting kit.
4. Re-install the door on top of the flush trim. The cam lock may require a minor adjustment in
order to compensate for the flush trim.
Function Selection
The following jumpers are available for function selection. Refer to Figure 2 on page 6 for location.
JW1: Cut for resettable +24V DC supply.
JW2: Cut to make auxiliary relay disconnectable.
JW3: Cut for normally open trouble contacts.
JW4: Cut for normally closed trouble contacts.