33
Notes:
Refer to outdoor unit service manual for request code 0 to 102, 106 to 149.
Request codes 103 to 105 indicate error histories of both indoor and outdoor units.
As only 4 digits can be displayed at one time the software version number is displayed in two halves.
Entercode190toseetherstfourdigitsandcode191toseethelast4digits.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
<Table9-4-1>
Request
code
Request content Range Unit
103 Errorhistory1(latest) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) Code
104 Errorhistory2(secondtolast) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) —
105 Errorhistory3(thirdtolast) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) —
154 Watercirculationpump1-Accumulatedoperatingtime(afterreset) 0–9999 10hours
156 Watercirculationpump2-Accumulatedoperatingtime(afterreset) 0–9999 10hours
157 Watercirculationpump3-Accumulatedoperatingtime(afterreset) 0–9999 10hours
158 Watercirculationpump4-Accumulatedoperatingtime(afterreset) 0–9999 10hours
162 Indoorunit-DIPSW1settinginformation Refer to detail contents described hereinafter. —
163 Indoorunit-DIPSW2settinginformation Refer to detail contents described hereinafter. —
164 Indoorunit-DIPSW3settinginformation Refer to detail contents described hereinafter. —
165 Indoorunit-DIPSW4settinginformation Refer to detail contents described hereinafter. —
166 Indoorunit-DIPSW5settinginformation Refer to detail contents described hereinafter. —
175 Indoorunit-Outputsignalinformation Refer to detail contents described hereinafter. —
176 Indoorunit-Inputsignalinformation Refer to detail contents described hereinafter. —
177 Mixingvalveopeningstep 0–10 Step
190 Indoorunit-Softwareversion1st4digits RefertoNotesbelow. —
191 Indoorunit-Softwareversionlast4digits RefertoNotesbelow. —
340 Watercirculationpump1-Accumulatedoperatingtimereset — —
342 Watercirculationpump2-Accumulatedoperatingtimereset — —
343 Watercirculationpump3-Accumulatedoperatingtimereset — —
344 Watercirculationpump4-Accumulatedoperatingtimereset — —
504 Indoorunit-Zone1roomtemp.(TH1A) −39–88 °C
505 Indoorunit-Ref.liquidtemp.(TH2) −39–88 °C
506 Indoorunit-Returnwatertemp.(THW2) −39–88 °C
507 Indoorunit-Zone2roomtemp.(TH1B) −39–88 °C
508 Indoorunit-DHWtankwatertemp.(THW5) −39–88 °C
509 Indoorunit-Zone1owwatertemp.(THW6) −39–88 °C
510 Indoorunit-Outsideairtemp.(TH7) −39–88 °C
511 Indoorunit-Flowwatertemp.(THW1) −39–88 °C
512 Indoorunit-Zone1returnwatertemp.(THW7) −39–88 °C
513 Indoorunit-Zone2flowwatertemp.(THW8) −39–88 °C
514 Indoorunit-Zone2returnwatertemp.(THW9) −39–88 °C
515 Indoorunit-Boilerflowwatertemp.(THWB1) −40–140 °C
516 Indoorunit-Boilerreturnwatertemp.(THWB2) −40–140 °C
540 Flowrateoftheprimarycircuit 0–100 L/min
550 Indoorunit-Errorpostponementhistory1(latest)
Displays postponement code.
("––"isdisplaysifnopostponementcodeispresent.)
—
551 Indoor unit - Operation control at time of error 0Standard,1Heater,2Boiler —
552
Indoor unit - Operation mode at time of error 0:OFF,1:DHW,2:Heating,3:Cooling,4:Legionellapreven-
tion,5:Freezeprotection,6:Operationstop,7:Defrost
—
553 Indoorunit-Outputsignalinformationattimeoferror Refer to detail contents described hereinafter. —
554 Indoorunit-Inputsignalinformationattimeoferror Refer to detail contents described hereinafter. —
555 Indoorunit-Zone1roomtemp.(TH1A)attimeoferror −39–88 °C
556 Indoorunit-Zone2roomtemp.(TH1B)attimeoferror −39–88 °C
557 Indoorunit-Ref.liquidtemp.(TH2)attimeoferror −39–88 °C
558 Indoorunit-Flowwatertemp.(THW1)attimeoferror −39–88 °C
559 Indoorunit-Returnwatertemp.(THW2)attimeoferror −39–88 °C
560 Indoorunit-DHWtankwatertemp.(THW5)attimeoferror −39–88 °C
561 Indoorunit-Zone1flowwatertemp.(THW6)attimeoferror −39–88 °C
562 Indoorunit-Zone1returnwatertemp.(THW7)attimeoferror −39–88 °C
563 Indoorunit-Zone2flowwatertemp.(THW8)attimeoferror −39–88 °C
564 Indoorunit-Zone2returnwatertemp.(THW9)attimeoferror −39–88 °C
565 Indoorunit-Boilerflowwatertemp.(THWB1)attimeoferror −40–140 °C
566 Indoorunit-Boilerreturnwatertemp.(THWB2)attimeoferror −40–140 °C
567
Indoorunit-Failure(P1/P2/L5/L8/Ld)thermistor 0:Failurethermistorisnone,1:TH1A,2:TH2,3:THW1,
4:THW2,5:THWB1,6:THW5,7:THWB2,8:TH1B,A:THW6,
B:THW7,C:THW8,D:THW9
—
568 Mixingvalveopeningstepattimeoferror 0–10 Step
569
OperatedFlowswitchattimeoffailure(L9) 0:Nooperatedflowswitch,1:Flowswitch1,2:Flowswitch2,
3:Flowswitch3
—
571 Flowrateattimeoferror 0–100 L/min