7 Applied Instructions
7.6 High Speed Processing
271
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
1
Outline
2
Instruction List
3
Configuration of
Instruction
4
How to Read
Explanation of
Instructions
5
Basic Instruction
6
Step Ladder
Instructions
7
Applied
Instructions
8
Interrupt Function
and Pulse Catch
Function
A
Relationships
between devices
and addresses
2. Instruction in which the digital filter is automatically changed
Regardless of the change in the filter time executed by the REFF instruction, when the following functions and
instructions are executed, the input filter value is automatically changed (as shown in the caution).
However, if the digital filter is used in any other functions or instructions than the ones listed, the digital filter
uses the time set in D8020. As a result, the program will not run correctly if the ON or OFF duration of the
corresponding input signal is less than the input filter time.
Input of interrupt pointer specified in the input interrupt function
Input used in a high speed counter
Input used in the SPD instruction