7 Applied Instructions
7.6 High Speed Processing
309
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
1
Outline
2
Instruction List
3
Configuration of
Instruction
4
How to Read
Explanation of
Instructions
5
Basic Instruction
6
Step Ladder
Instructions
7
Applied
Instructions
8
Interrupt Function
and Pulse Catch
Function
A
Relationships
between devices
and addresses
2. Monitoring the current number of generated pulses
The number of pulses output from Y000 or Y001 is stored in the following special data resistors.
*1. The FX
0, FX0S, FX0N, FXU or FX2C PLC is not compatible with this function.
*2. The FX
0, FX0S or FX0N PLC is not compatible with this function.
The FX
U PLC of V3.07 or later is compatible.
The contents of each data register can be cleared using the following program.
3. How to stop the pulse output
When the command input is set to OFF, the pulse generation is immediately stopped. When the command
input is set to ON again, pulse generation operation restarts from the beginning.
When the special auxiliary relays (M) shown below are set to ON, the pulse output is stopped.
To restart pulse output, set the device corresponding to the output signal to OFF, and then drive the pulse
output instruction again.
Device
Description Contents of data
High order Low order
D8141
*1
D8140
*1
Accumulated number of pulses
output from Y000
Accumulated number of pulses output from Y000 by PLSY and PLSR
instructions
D8143
*1
D8142
*1
Accumulated number of pulses
output from Y001
Accumulated number of pulses output from Y001 by PLSY and PLSR
instructions
D8137
*2
D8136
*2
Total accumulated number of
pulses output from Y000 and Y001
Total accumulated number of pulses output from Y000 and Y001 by
PLSY and PLSR instructions.
Device
Description
FX3U, FX3UC FX3G FX1S, FX1N, FX1NC
M8349 M8145, M8349 M8145 Immediately stops pulse output from Y000.
M8359 M8146, M8359 M8146 Immediately stops pulse output from Y001.
Command
input
DMOV
EN
s
ENO
d
Label 1
*3
Label 2
*4
*3. This defines K0.
*4. This defines the low order devices in the table above.