7 Applied Instructions
7.7 Handy Instruction
344
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
2) M0 output is turned ON when command contact is turned ON.
3) Output (M0) is reset when the present value of C0 reaches comparative value D300, and the count value
of the process counter C1 is incremented by +1, and the present value of the counter C0 is also reset.
4) Next output M1 is turned ON.
5) Output M1 is compared with comparative value D301 of C0 present value, and when reaching the
comparative value, the count value of the process counter C1 is incremented by +1, and the present
value of the counter C0 is also reset.
6) Similarly compared up to the number of points designated in n(K4). (1 ≤ n ≤ 64)
7) When the final process designated in n is over, execution complete flag M8029 is turned ON for one
operation period.
M8029 is a command execution complete flag used by a plurality of commands, and is used as the
contact right after the command, and then you can set up a complete flag exclusively for this command.
8) Repeat outputs by returning to the beginning.
Cautions
1. When designating the digits of bit device in the device designated in 
Designate a multiple of 16 (0, 16, 32, 64, ...) in the device number.
2. Object devices are limited.
S1: FX3U, FX3UC PLCs only are applicable.  
However, index modifier (V, Z) is not applicable.
S2: FX
3U, FX3UC, FX3G PLCs only are applicable.
S3: FX
3U, FX3UC PLCs only are applicable.