7 Applied Instructions
7.7 Handy Instruction
346
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
Function and operation explanation
1. 16-bit operation(TTMR)
The pushing duration of command input (pushbutton) is measured in the unit of seconds, and is multiplied by
multiplying factor (10
n
), and transferred to the device designated in .
The time to be transferred to the device designated in depends on the multiplying factor of n, supposing
the pushing duration to be τ0 (1 sec unit), and the value of the device actually designated in is as
follows.
Related command
You can use such a convenient command.
Cautions
1. When command contact is turned OFF
The present value ( +1) of the pushing duration is reset, and the teaching time is not changed.
2. Number of bits occupied
Two devices are occupied starting from the device (teaching time) designated in .
Be careful not to overlap with the device used in control of the machine.
: Teaching time
+1: Present time of pushing duration
3. Object devices are limited.
S1: FX3U, FX3UC PLCs only are applicable.
Multiplying factor
K0 τ0
×1
K1 10τ0
×10
K2 100τ0
×100
Command Content
HOUR
The command to issue the ON time of HOUR command by the time added and designated in 1
hour unit.
Command
contact
+1
τ0τ0
Pushing duration (sec) Pushing duration (sec)
+1
Command input
TTMR
EN
n
ENO
d
d
d
d
d
Multiplying factor number
to be applied to teaching
data
Device for storing
teaching data