3 ANALOG OUTPUT MODULE FB
3.3 M+FX5-4DA_WaveOutputSetting
17
3
Output label
FB details
(9) i_uConvSpeed Waveform output
conversion cycle
constant
Word [Unsigned] 1 to 5000 Sets the constant that defines the conversion cycle of
wave output.
(10) i_uUnitType Module type Word [Unsigned] 0: FX5-4DA Specifies a module type.
No. Variable name Name Data type Default value Description
(11) o_bENO Execution status Bit OFF ON: The execution command is ON.
OFF: The execution command is OFF.
(12) o_bOK Normal completion Bit OFF The on state indicates that setting the wave output has
been completed.
(13) o_bErr Error completion Bit OFF The on state indicates that an error has occurred in the
FB.
(14) o_uErrId Error code Word [Unsigned] 0 The error code of an error occurred in the FB is stored.
Item Description
Available device Target module FX5-4DA
Target CPU FX5U CPU, FX5UC CPU
Engineering tool GX Works3 Version 1.040S or later
Language Ladder diagram
Number of basic steps 295 steps
The number of FB steps integrated in the program varies depending on the CPU module used, the input/output definition, and
the setting options of GX Works3. For the setting options of GX Works3, refer to GX Works3 Operating Manual.
Processing As i_bEN (execution command) turns on, the wave output settings of a specified channel or all channels are written.
The wave output setting is enabled only when the output mode setting is set to the wave output mode. The wave data for
analog output is required to be set in advance.
The set value is enabled by turning on and off 'Operating condition setting request' (Un\G70.b9) or executing the operating
condition setting request operation FB (M+FX5-4DA _RequestSetting).
When the setting values of target channel are out of range, o_bErr (Error completion) turns on, and the FB processing are
stopped. Also, Error code 100 (Hexadecimal) is stored in o_uErrId (Error code). For the error code, refer to Page 18
Error code.
When the setting values of module type are out of range, o_bErr (Error completion) turns on, and the FB processing are
stopped. Also, Error code 102 (Hexadecimal) is stored in o_uErrId (Error code). For the error code, refer to Page 18
Error code.
FB compilation method Macro type
FB operation Pulsed execution (single scan execution type)
No. Variable name Name Data type Range Description