APPENDIX
Appendix 5 I/O Module
173
A
Output specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature.
For details, refer to Page 26 Input/Output Derating Curve
■Relay output
■Transistor output (sink output)
Item Specifications
No. of output points FX5-8EYR/ES 8 points
FX5-16EYR/ES 16 points
FX5-32ER/S 16 points
Connection type Terminal block (M3 screws)
Output type Relay
External power supply 30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE UL, cUL standards)
Output circuit insulation Mechanical insulation
Indication of output operation LED is lit when output is on
Max. load 2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
Open circuit leakage current
Min. load 5 V DC, 2 mA (reference values)
Response time OFFON Approx. 10 ms
ONOFF Approx. 10 ms
Output circuit configuration
Item Specifications
No. of output points FX5-8EYT/ES 8 points
FX5-16EYT/ES 16 points
FX5-32ET/S16 points
FX5-16ET/ES-H 8 points
FX5-C16EYT/D 16 points
FX5-C32EYT/D 32 points
FX5-C32ET/D 16 points
Connection type FX5-EYT/ES,
FX5-32ET/S,
FX5-16ET/ES-H
Terminal block (M3 screws)
FX5-CEYT/D,
FX5-C32ET/D
Connector
Output type Transistor/sink output
External power supply 5 to 30 V DC
Output circuit insulation Photo-coupler insulation
Indication of output operation LED is lit when output is on
• With FX5-C32EYT/, the lower number/higher number order is switched with the DISP switch F/L.
• With FX5-C32ET/, the input/output is switched with the DISP switch IN/OUT.
Load
Fuse
Fuse
Y
COM0
Y
COM1
AC power
supply
DC power
supply