6 WIRING
6.6 Output Wiring
Triac output
For output specifications of the terminal modules, refer to Page 188 Output specifications.
Handling of triac output
Output terminal
Four triac output points are covered by one common terminal. The common terminal blocks can drive loads of different circuit
voltage systems (Example: 100 V AC and 24 V DC).
Insulation of circuit
The internal circuit and the output element (triac) are insulated with photothyristors.
The common blocks are separated from one another.
Display of operation
The LED turns on and the output triac is turned on when photothyristors are actuated.
Response time
The response time until the output triac is turned on after the photothyristors are actuated (or shut off) is 1 ms or less, and the
response time until the output triac is turned off is 10 ms or less.
Output current
Current of 0.3 A can flow per one output point. However, current of four output points should be 0.8 A (average of 0.2 A per
one point) to suppress temperature rise. When a load with a high rush current is frequently turned on or off, the mean-square
current should be 0.2 A or less.
Open circuit leakage current
C-R absorbers are connected in parallel at the triac output terminal for turning off the triac. Thus, open circuit leakage currents
of 1 mA/100 V AC or 2 mA/200 V AC occurs. Since the triac output type has open circuit leakage currents, even after the triac
output is turned off, a small relay and a minute current load with low rated operation currents may continuously operate.
Therefore, the load should be equal to or more than 0.4 VA/100 V AC or 1.6 VA/200 V AC. For loads lower than these values,
connect the surge absorbers described later in parallel.
Load
100 V AC
U
Fuse
Y0
Y1
COM1
Load
200 V AC
U
Fuse
Y0
Y1
COM2
Terminal module
0.4 A
0.7
seconds
4 A
10
seconds
0.02
seconds
0.02 + 0.7 + 10
4
2
0.02 + 0.4
2
0.7
= 0.2 A
<Example>