188
APPENDIX
Appendix 8 Terminal Module
Output specifications
■Relay output (FX-16EYR-TB, FX-16EYR-ES-TB/UL)
Item Specifications
Output type Relay
External voltage 250 V AC or less, 30 V DC or less
Max. load Resistance load 2 A/point The total load current per common terminals (four points) should be 8 A or less.
Inductive load 80 VA
Min. load 5 V DC, 2 mA (reference values)
Open circuit leakage current
Response time Approx. 10 ms
ON voltage of output element 1.5 V
Insulation of circuit Mechanical insulation
Indication of output operation LED is lit when the power is supplied to relay coils.
Power consumption 1.92 W (80 mA 24 V DC)
Input/output configuration circuit FX-16EYR-TB
FX-16EYR-ES-TB/UL
Unsupported applications Positioning, Pulse Y Output ((D)PLSY) instruction, Pulse Width Modulation ((D)PWM) instruction,
ABS Current Value Read (DABS) instruction, Start/stop of high-speed I/O function ((D)HIOEN)
instruction, Input Matrix (MTR) instruction, Digital Switch (DSW) instruction, Seven Segment With
Latch (SEGL) instruction
0 to 7
COMn
External wiring
LED
24 V DC 5 mA
Fuse
24+
CN1
connector
side
0 to 7
COMn
External wiring
LED
24 V DC 5 mA
Fuse
24-
CN1
connector
side