2 SPECIFICATIONS
2.1 Performance Specifications
17
2
2 SPECIFICATIONS
This chapter describes the performance specifications.
2.1 Performance Specifications
This section describes the performance specifications of temperature input modules.
Thermocouple input module
*1 Except for the conditions under noise influence.
*2 This conversion speed is the time required to store a measured temperature value into the buffer memory in sampling processing.
*3 No isolation is provided between the cold junction compensation channel and the programmable controller power supply.
*4 A count more than 50000 times causes Number of writes to offset/gain settings reach limit error (error code: 1080H).
Item Specifications
Model R60TD8-G
Number of analog input channels 8 channels + Cold junction compensation channel per module
Output Measured temperature value 16-bit signed binary value (-2700 to 18200)
Scaling value 16-bit signed binary value
Compliant thermocouple standard JIS C1602-1995, IEC 60584-1(1995), IEC60584-2(1982)
Usable thermocouples and conversion accuracy For details, refer to the following.
Page 40 Usable thermocouple, conversion accuracy, and effect per wiring resistance 1Ω
Cold junction compensation accuracy 1.0
Accuracy
*1
For details, refer to the following.
Page 40 Accuracy of the thermocouple input module
Resolution B, R, S, N: 0.3
K, E, J, T: 0.1
Conversion speed
*2
30ms/channel
Isolation method
*3
Between thermocouple input channel and
programmable controller power supply
Transformer isolation
Between thermocouple input channels Transformer isolation
Withstand voltage Between thermocouple input channel and
programmable controller power supply
500VACrms for 1 minute
Between thermocouple input channels 1000VACrms for 1 minute
Insulation
resistance
Between thermocouple input channel and
programmable controller power supply
500VDC 10M or higher
Between thermocouple input channels 500VDC 10M or higher
Disconnection detection Built-in
Number of offset/gain settings
*4
50000 times maximum
Number of occupied I/O points 16 points (I/O assignment: Intelligent 16 points)
External interface 40-pin connector
Applicable wire
size
When A6CON1 and A6CON4 are used 0.088 to 0.3mm
2
(28 to 22 AWG) (stranded wire)
When A6CON2 is used 0.088 to 0.24mm
2
(28 to 24 AWG) (stranded wire)
Connector for external devices A6CON1, A6CON2, A6CON4 (sold separately)
Internal current consumption (5VDC) 0.36A
External
dimensions
Height 106mm
Width 27.8mm
Depth 110mm
Weight 0.19kg