18
2 SPECIFICATIONS
2.1 Performance Specifications
RTD input module
*1 An usable resistance temperature detector is 3-wire type only. A resistance temperature detector of 2-wire type or 4-wire type cannot be
used.
*2 When a value outside the input range is input from a resistance temperature detector, the value is regarded as the maximum value or
minimum value of the input range.
*3 The accuracy when a resistance temperature detector is connected, refer to the following.
Page 42 Accuracy of the RTD input module
*4 This conversion speed is the time required to store a measured temperature value into the buffer memory in sampling processing.
*5 A count more than 50000 times causes Number of writes to offset/gain settings reach limit error (error code: 1080H).
Item Specifications
Model R60RD8-G
Number of analog input channels 8 channels
Output Measured temperature value 16-bit signed binary value (-2000 to 8500)
Scaling value 16-bit signed binary value
Usable resistance temperature detector
*1
Pt100 (JIS C 1604-2013, IEC 751:1983)
JPt100 (JIS C 1604-1981)
Ni100 (DIN 43760 1987)
Pt50 (JIS C 1604-1981)
Temperature
measuring range
Pt100 -200 to 850
JPt100 -180 to 600
Ni100 -60 to 250
Pt50 -200 to 650
Output current for temperature detection 1.0mA or lower
Conversion
accuracy
*2*3
Pt100 -200 to 850 0.8 (ambient temperature: 255), 2.4 (ambient temperature: 0 to 55)
-20 to 120 0.3 (ambient temperature: 255), 1.1 (ambient temperature: 0 to 55)
0 to 200 0.4 (ambient temperature: 255), 1.2 (ambient temperature: 0 to 55)
JPt100 -180 to 600 0.8 (ambient temperature: 255), 2.4 (ambient temperature: 0 to 55)
-20 to 120 0.3 (ambient temperature: 255), 1.1 (ambient temperature: 0 to 55)
0 to 200 0.4 (ambient temperature: 255), 1.2 (ambient temperature: 0 to 55)
Ni100 -60 to 250 0.4 (ambient temperature: 255), 1.
2 (ambient temperature: 0 to 55)
Pt50 -200 to 650 0.8 (ambient temperature: 255), 2.4 (ambient temperature: 0 to 55)
Resolution 0.1
Conversion speed
*4
10ms/channel
Isolation method Between RTD input channel and
programmable controller power supply
Transformer isolation
Between RTD input channels Transformer isolation
Withstand voltage Between RTD input channel and
programmable controller power supply
500VACrms for 1 minute
Between RTD input channels 1000VACrms for 1 minute
Insulation
resistance
Between RTD input channel and
programmable controller power supply
500VDC 10M or higher
Between RTD input channels 500VDC 10M or higher
Disconnection detection Built-in
Number of offset/gain settings
*5
50000 times maximum
Number of occupied I/O points 16 points (I/O assignment: Intelligent 16 points)
External interface 40-pin connector
Applicable wire
size
When A6CON1 and A6CON4 are used 0.088mm
2
to 0.3mm
2
(28 to 22 AWG) (stranded wire)
When A6CON2 is used 0.088mm
2
to 0.24mm
2
(28 to 24 AWG) (stranded wire)
Connector for external devices A6CON1, A6CON2, A6CON4 (sold separately)
Internal current consumption (5VDC) 0.35A
External
dimensions
Height 106mm
Width 27.8mm
Depth 110mm
Weight 0.19kg