6 - 12
(5) Precautions
Table6.3 shows the output status of the CPU module when the operating status is changed from STOP
to RUN after the outputs (Y) are forcibly turned on in the STOP status.
Table6.3 Output status when the operating status is changed from STOP to RUN after the output forced on operation is performed
Outputmode("OutputmodeatSTOPtoRUN")selected Outputstatus
Previous state
The output status prior to STOP is output.
Even if the outputs are forcibly turned on, the on status is not held if
the output status prior to STOP was off.
Recalculate (output is 1 scan later) The on status is held and output.