6 - 44
(d) Cancelling on/off registration data
The registered forced ON/OFF data can be canceled by GX Developer.
Once the registered data is canceled, the status of the forced on/off registered devices will be as follows.
Forced on/off setting can be cleared by:
powering off and then on the CPU module,
resetting the CPU module by the RUN/STOP/RESET switch, or
resetting the CPU module by the remote RESET operation.
(e) External input/output forced on/off timing
Table6.13 shows the external input/output forced on/off timing.
Table6.12 Status of devices after forced on/off registration data is canceled
Forcedon/offregistereddevice
Sequenceprogramoperations
(on/off)performed
Sequenceprogramoperations
(on/off)notperformed
Input
Input from modules mounted on the base unit Uses the on/off status input from modules.
Input of the CPU module to be refreshed from LX
of a CC-Link IE controller network or
MELSECNET/H module
Used the on/off status refreshed via CC-Link IE controller network or
MELSECNET/H.
Input of the CPU module to be refreshed from
RX of a CC-Link module
Uses the on/off status refreshed via CC-Link.
Input other than above (outside of the refresh
range)
Uses the results of sequence
program operations.
Holds the forced on/off status.
Output
Output from modules mounted on the base unit
Outputs the results of sequence
program operations.
Holds the registered on/off status.
Output of the CPU module to be refreshed from
LX of a CC-Link IE controller network or
MELSECNET/H module
Output of the CPU module to be refreshed from
RX of a CC-Link module
Output other than above (outside of the refresh
range)
Outputs the results of sequence
program operations. (The results
are not output externally.)
Holds the forced on/off status.
Table6.13 Forced on/off timing
Refresharea Input Output
Input and output of
modules mounted on the
base unit
During END processing (input refresh)
At execution of the COM instruction (input refresh)
At execution of an instruction using direct access
input (DX) (LD, LDI, AND, ANI, OR, ORI, LDP, LDF,
ANDP, ANDF, ORP, ORF)
At execution of the RFS or MTR instruction
At execution of an instruction used for a system
interrupt (UDCNT1, UDCNT2, SPD)
During END processing (output refresh)
At execution of the COM instruction (output
refresh)
At execution of an instruction using direct access
input (DX) (OUT, SET, DELTA, RST, PLS, PLF,
FF, MC, SFT)
At execution of the RFS or MTR instruction
At execution of an instruction used for a system
interrupt (PLSY, PWM)
Input and output of the CPU
module to be refreshed from
LX/LY of a CC-Link IE
controller network or
MELSECNET/H module
During END processing (refresh via CC-Link IE controller network or MELSECNET/H)
At execution of the COM instruction
At execution of the ZCOM instruction
Input and output of the CPU
module to be refreshed from
RX/RY of a CC-Link module
During END processing (auto refresh)
At execution of the COM instruction (auto refresh)
At execution of the ZCOM instruction (auto refresh)