12 - 65
*1: The relevant modules are as follows:
• The Universal model QCPU whose serial number (first five digits) is "10102" or later.
• Q00UJCPU, Q00UCPU, Q01UCPU
Table12.28 Special register
ACPU 
Special 
Register
Special 
Register 
after 
Conversion
Special 
Register for 
Modification
Name Meaning Details
Corresponding 
CPU
D9009 SD1009 SD62
Annunciator 
detection
F number at which 
external failure has 
occurred
• When one of F0 to 2047 is turned on by OUT F or 
SET F instruction, the F number, which has been detected earliest 
among the F numbers which have turned on, is stored in BIN code.
• SD1009 can be cleared by RST F or LEDR instruction. 
If another F number has been detected, the clearing of SD1009 
causes the next number to be stored in SD1009.
Qn(H)
QnPH
QnU
*1
D9010 SD1010 Error step
Step number at which 
operation error has 
occurred.
• When operation error has occurred during execution of application 
instruction, the step number, at which the error has occurred, is 
stored in BIN code. 
Thereafter, each time operation error occurs, the contents of 
SD1010 are renewed.
Qn(H)
QnPH
D9011 SD1011 Error step
Step number at which 
operation error has 
occurred.
• When operation error has occurred during execution of application 
instruction, the step number, at which the error has occurred, is 
stored in BIN code. Since the step number is stored into SD1011 
when SM1011 turns from OFF to ON, the data of SD1011 is not 
updated unless SM1011 is cleared by a user program.
D9014 SD1014
I/O control 
mode
I/O control mode 
number
• The I/O control mode set is returned in any of the following 
numbers:
0: Both input and output in direct mode
1: Input in refresh mode, output in direct mode
3: Both input and output in refresh mode
D9015 SD1015 SD203
Operating 
status of CPU
Operating status of 
CPU
• The operation status of CPU as shown below are stored in 
SD1015.
*1:  When the CPU mdoule is in RUN mode and SM1040 is off, the 
CPU module remains in RUN mode if changed to PAUSE mode.
Qn(H)
QnPH
QnU
*1
b15 b12
to
b11 b8
to
b7 b4
to
b3 b0
to
0
1
2
RUN
PAUSE
STOP
Remote RUN/STOP 
by parameter setting
0
1
2
RUN
PAUSE
STOP
Remote RUN/STOP 
by computer
0
1
2
RUN
PAUSE
3
STEP RUN
STOP
CPU key switch
0
1
Except below
Instruction 
execution
Status in program
Remains the same in 
remote RUN/STOP 
mode.
STOP
1
1
1