7 69-2426—01
Installer setup tables
Setup function Settings & options (factory default in bold)
134 Central Controller
(AG-150 or similar)
Present
0 Not Installed
1 Installed
136 Residential/Commercial 1 Commercial
0 Residential
138 Permanent Hold Lock
(Non-programmable)
0 OFF (Programmable)
1 ON(Non-programmable)
139 Fahrenheit/Celsius
Display
0 Fahrenheit
1 Celsius
140 Commercial Override
Duration
3 3 Hours
0 OFF
1–12 1–12Hours
142 System Type 0 Heat & Cool (Heat Pump)
1 CoolOnly
144 System Changeover 1 System Changeover (Auto, Heat, Off, Cool)
0 ManualChangeover(Heat,Off,Cool)
2 SystemChangeoverOnly(AutoOnly)
3 System Changeover Single Setpoint - only with AG-150 or
similar(Auto,Heat,Off,Cool)
145 System Changeover
Deadband Value
3 3 °F (2 °C)
2–8 2–8°F(1.5–4.5°C)
146 Drying Mode 0 OFF
1 ON
148 Schedule Format 0 5-2
1 5-1-1
150 Optimal Start 1 ON
0 OFF
152 Scheduled Off 0 Not Shown * See page 9 for feature information
1 Shown
154 Power Off Timer
("Sleep Timer")
0 Not Shown
1 Resumeoperationatnextscheduledperiod
2 PermanentlyOffuntiluserchangesSystemmode
160 Full Lockout 0 No
1 Yes
162 Lockout On/Off 0 No
1 Yes
164 Lockout System Mode
(Heat, Cool, Auto,
Drying)
0 No
1 Yes
165 Lockout Fan Mode 0 No
1 Yes
166 Lockout Setpoint 0 No
1 Yes
168 Lockout Set Clock/Day/
Schedule
0 No
1 Yes
170 Max Heat Setpoint 90 90 °F (32 °C) * Subject to
40–89 40to89°F(4.5to31.5°C) HVAC Equipment
172 Min Cool Setpoint 50 50 °F (10 °C) * Subject to
51–99 51to99°F(10.5to37°C) HVAC Equipment
173 Sensing Location 1 Sense at Remote Controller
0 Sense at Indoor Unit
174 Indoor Temperature
Display Offset
0 0 °F (0 °C)
-3to3°F(-1.5to1.5°C)