12 FUNCTION SETTING
Function
Settings
Mode No.
Setting No.
: Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting 1
LOSSNAY
connectivity
Power supply
voltage
Auto operating
mode
Frost prevention
temperature
Humidifier control
Change of
defrosting control
OFF
ON
Average data from each indoor unit
Data from the indoor unit with remote controller
Data from main remote controller
Not supported
Supported
(Indoor unit does not intake outdoor air through LOSSNAY
)
Supported
(Indoor unit intakes outdoor air through LOSSNAY)
240V
220V, 230V
Auto energy-saving operation ON
Auto energy-saving operation OFF
2 (Normal)
3
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Standard
For high humidity
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
1
2
01
02
03
04
05
15
16
17
The setting is
applied to all
the units in the
same
refrigerant
system.
12-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 set the indoor unit number.)
Meaning of "Function setting"
Mode02:indoor temperature detecting
No.
Indoor temperature(ta)=
No.1
Average data of the
sensor on all the
indoor units
Initial
setting
ta=(A+B)/2 ta=(A+B)/2 ta=A ta=A
No.2
The data of the sensor
on the indoor unit that
connected with
remote controller
ta=A ta=B ta=A ta=A
No.3
The data of the sensor
on main remote
controller
ta=C ta=C ta=C ta=C
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
INDOOR
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
OUTDOOR
INDOOR
REMOTE
(MAIN)
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
INDOOR
W1 The functions below are available only when the wired remote controller is used. The functions are not available for floor
standing models.
OCH424E

Other manuals for Mitsubishi Electric PUHZ-P200YHA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric PUHZ-P200YHA and is the answer not in the manual?

Mitsubishi Electric PUHZ-P200YHA Specifications

General IconGeneral
BrandMitsubishi Electric
ModelPUHZ-P200YHA
CategoryAir Conditioner
LanguageEnglish

Related product manuals