EasyManua.ls Logo

Mitsubishi Electric Q01UCPU - Remote Operation; Remote RUN;STOP

Mitsubishi Electric Q01UCPU
580 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
129
CHAPTER 3 FUNCTIONS
3
3.6 Remote Operation
3.6.1 Remote RUN/STOP
3.6 Remote Operation
The remote operation can change the operating status of the CPU module externally (using a programming tool,
external devices in the MC protocol, link dedicated instructions for a CC-Link IE module or a MELSECNET/H module,
or remote contacts). Four types of remote operations are available:
Remote RUN/STOP ( Page 129, Section 3.6.1)
Remote PAUSE ( Page 132, Section 3.6.2)
Remote RESET ( Page 134, Section 3.6.3)
Remote latch clear ( Page 135, Section 3.6.4)
3.6.1 Remote RUN/STOP
This operation changes the operating status of the CPU module externally to RUN or STOP, keeping the
RUN/STOP/RESET switch of the CPU module in the RUN position.
(1) Application
This operation is useful to run or stop the CPU module remotely when:
the CPU module is inaccessible, or
the CPU module is in a control panel.
(2) Program operation
The program operation will be as follows when the remote RUN/STOP operation is performed.
(a) Remote STOP
The CPU module executes a program until the END instruction and changes its operating status to STOP.
(b) Remote RUN
The CPU module changes its operating status to RUN and executes a program from the step 0.

Table of Contents

Related product manuals