149
CHAPTER 6 CPU MODULE
6
6.2 Specifications
6.2.2 High Performance model QCPU
*5 The CPU module can execute up to 124 programs. Any program exceeding 124 cannot be executed.
*6 The number has been increased by the function upgrade of the CPU module.
( Qn(H)/QnPH/QnPRHCPU User's Manual (Function Explanation, Program Fundamentals))
*7 The number of points can be changed within the setting range.
( Qn(H)/QnPH/QnPRHCPU User's Manual (Function Explanation, Program Fundamentals)
*12 When the Q2MEM-2MBS is used, the maximum number of files stored is 287 for the CPU module whose serial number
(first five digits) is "16020" or earlier.
Item
High Performance model QCPU
Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU
Max. number
of files stored
Program memory 28 60 124
252
*5
Memory card (RAM)
319 (When the Q3MEM-4MBS is used)
*12
Memory
card
(ROM)
Flash
card
288
ATA card 512
Standard RAM
3
*6
Standard ROM 28 60 124 252
Max. number of intelligent
function module
parameters
Initial
setting
512
Refresh 256
No. of times of writing data into the
standard ROM
Max. 100000 times
No. of I/O device points
(No. of points usable on program.)
8192 points (X/Y0 to 1FFF)
No. of I/O points
(No. of points accessible to the actual
I/O module.)
4096 points (X/Y0 to FFF)
No. of device points
*7
Internal relay [M] 8192 points by default (M0 to 8191) (changeable)
Latch relay [L] 8192 points by default (L0 to 8191) (changeable)
Link relay [B] 8192 points by default (B0 to 1FFF) (changeable)
Timer [T]
2048 points by default (T0 to 2047) (sharing of low- and high-speed timers) (changeable)
The low- and high-speed timers are specified by the instructions.
The measurement unit of the low- and high-speed timers is set up by parameters.
(Low-speed timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed timer: 0.1 to 100.0ms, 0.1ms unit, 10.0ms by default)
Retentive timer [ST]
0 point by default (sharing of the low- and high-speed retentive timers) (changeable)
The low- and high-speed retentive timers are specified by the instructions.
The measurement unit of the low- and high-speed retentive timers is set up by parameters.
(Low-speed retentive timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed retentive timer: 0.1 to 100.0ms, 0.1ms unit, 10.0ms by default)
Counter [C]
Normal counter, 1024 points by default (C0 to 1023) (changeable)
Interrupt counter: 256 points max. (0 point by default, setting by parameters)
Data register [D] 12288 points by default (D0 to 12287) (changeable)
Link register [W] 8192 points by default (W0 to 1FFF) (changeable)
Annunciator [F] 2048 points by default (F0 to 2047) (changeable)
Edge relay [V] 2048 points by default (V0 to 2047) (changeable)