150
*8 When a Flash card is used, only reading is possible. ATA cards cannot be used.
*9 The step relay is a device for the SFC function.
*13 The card can be used for the CPU module whose serial number (first five digits) is "16021" or later.
Item
High Performance model QCPU
Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU
No. of device points
File
register
*8
[R],
[ZR]
R: The following number of device points can be used by switching blocks (in increments of
32768 points (R0 to 32767)).
ZR: The following number of device points can be used without switching blocks.
Standard
RAM
32768 points 65536 points 131072 points
SRAM card
(1M byte)
517120 points
SRAM card
(2M bytes)
1041408 points
SRAM card
(4M bytes)
*13
1042432 points
Flash card
(2M bytes)
1041408 points
Flash card
(4M bytes)
1042432 points
Link special relay [SB] 2048 points (SB0 to 7FF) (The number of device points is fixed.)
Link special register [SW] 2048 points (SW0 to 7FF) (The number of device points is fixed.)
Step relay [S]
*9
8192 points (S0 to 8191) (The number of device points is fixed.)
Index register [Z] 16 points (Z0 to 15) (The number of device points is fixed.)
Pointer [P]
4096 points (P0 to 4095) (The number of device points is fixed.), The use ranges of the local
pointers and common pointers can be set up by parameters.
Interrupt pointer [I]
256 points (I0 to 255) (The number of device points is fixed.)
The constant cyclic interval of system interrupt pointers I28 to 31 and I49 can be set up by
parameters.
(I28 to 31: 0.5 to 1000ms, in 0.5ms unit, I49: 0.2 to 1.0ms, in 0.1ms unit)
Default values I28: 100ms, I29: 40ms, I30: 20ms, I31: 10ms, I49: Blank
Special relay [SM] 2048 points (SM0 to 2047) (The number of device points is fixed.)
Special register [SD] 2048 points (SD0 to 2047) (The number of device points is fixed.)
Function input [FX] 16 points (FX0 to F) (The number of device points is fixed.)
Function output [FY] 16 points (FY0 to F) (The number of device points is fixed.)
Function register [FD] 5 points (FD0 to 4) (The number of device points is fixed.)
No. of device tracking words ----
Link direct device
Device for accessing the link device of a network module directly
Specified form: J\X, J\Y, J\W, J\B, J\SW, J\SB
Intelligent function module device
Device for accessing the buffer memory of the intelligent function module directly.
Specified form: U\G