322
1413
[CONTROL-BUS ERR.]
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• The cause is a failure of the intelligent
function module, CPU module, or base
unit. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
[CONTROL-BUS ERR.]
(1) An error is detected on the system bus.
• Self-diagnostic error in the system bus
• Self-diagnostic error in the CPU module
(2) In a multiple CPU system, the control CPU
setting of other CPUs, configured in the I/O
Assignment tab of "PLC Parameter", differs
from that of CPU No.1.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
• Reconfigure the control CPU setting of
other CPUs so that it can be the same as
that of CPU No.1.
QCPU
1414
[CONTROL-BUS ERR.]
• Fault of a loaded module was detected.
• In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• Always
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
[CONTROL-BUS ERR.]
An error is detected on the system bus.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• Always
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
1415
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
■Co
llateral information
• Common information: Module No. (Base No.)
• Individual information: -
■Diagnostic timing
• Always
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset/When an END instruction
executed
Qn(H)
*7
QnPH
*7
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU