322
1413
[CONTROL-BUS ERR.]
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
The cause is a failure of the intelligent
function module, CPU module, or base
unit. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
[CONTROL-BUS ERR.]
(1) An error is detected on the system bus.
Self-diagnostic error in the system bus
Self-diagnostic error in the CPU module
(2) In a multiple CPU system, the control CPU
setting of other CPUs, configured in the I/O
Assignment tab of "PLC Parameter", differs
from that of CPU No.1.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
Reconfigure the control CPU setting of
other CPUs so that it can be the same as
that of CPU No.1.
QCPU
1414
[CONTROL-BUS ERR.]
Fault of a loaded module was detected.
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
Always
Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnU
[CONTROL-BUS ERR.]
An error is detected on the system bus.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
Always
Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
1415
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
Co
llateral information
Common information: Module No. (Base No.)
Individual information: -
Diagnostic timing
Always
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset/When an END instruction
executed
Qn(H)
*7
QnPH
*7
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents