323
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.3 List of error codes (1000 to 1999)
1416
[CONTROL-BUS ERR.]
An error was detected on the system bus.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnU
[CONTROL-BUS ERR.]
An error was detected on the system bus in the
multiple CPU system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Q00CPU
Q01CPU
QnU
1417
[CONTROL-BUS ERR.]
A reset signal error was detected on the system
bus.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1418
[CONTROL-BUS ERR.]
In the debug mode, both the main base unit for
system A and the main base unit for system B
are connected to an extension base unit.
In the redundant system, the control system
cannot access the extension base unit because
it has failed to acquire an access right.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-ON/At reset/At Switching execution
Check that both the main base unit for
system A and the main base unit for
system B are not connected to an
extension base unit in the debug mode.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, Q6WRB, or extension cable.
Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
1430
[MULTI-C.BUS ERR.]
The error of host CPU is detected in the multiple
CPU high speed transmission.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
1431
[MUL
TI-C.BUS ERR.]
The communication error with other CPU is
detected in the multiple CPU high speed
transmission.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Take noise reduction measures.
Check the main base unit mounting status
of the CPU module.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
1432
[MULTI-C.BUS ERR.]
The communication time out with other CPU is
detected in the multiple CPU high speed
transmission.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU