332
2100
[SP.UNIT LAY ERR.]
In the I/O Assignment tab of "PLC Parameter",
"Intelligent" (intelligent function module) or a
branch module is set for the position where an
I/O module is connected.
In the I/O Assignment tab of "PLC Parameter",
"Input" (input module), "Output" (output
module), or a branch module is set for the
position where an intelligent function module is
connected.
In the I/O Assignment tab of "PLC Parameter",
"Input" (input module), "Output" (output
module), or "Intelligent" (intelligent function
module) is set for the position where a branch
module is connected.
In the I/O Assignment tab of "PLC Parameter",
switch settings are configured for the module
that does not support the setting.
In the I/O Assignment tab of "PLC Parameter",
the number of points assigned to the intelligent
function module is less than that of the mounted
module.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Set the I/O assignment again so that the
setting matches with the mounting status of
the intelligent function module, CPU
module, or branch module.
Delete the switch setting in the I/O
assignment setting tab of "PLC parameter".
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
[SP.UNIT LAY ERR.]
In the PLC parameter setting, setting content for
the adapter type is different from the ones for the
mounted adapter. Or no adapter has been set.
Collateral information
Common information: FFFF
H
(fixed)
Individual information: -
Diagnostic timing
At power-on/At reset
Make setting again to match the PLC
parameter adapter type setting with the
mounted adapter.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, RS-232 adapter, and RS-422/485
adapter. Please consult your local
Mitsubishi representative.
LCPU
2101
[SP.UNIT LAY ERR.]
13 or more A-series special function modules
(except for the A1SI61/AI61(-S1)) that can initiate
an interrupt to the CPU module have been
installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of A series special
function modules (except the A1SI61/AI61(-
S1)) that can start interrupt programs to the
CPU module to 12 or less.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
2102
[SP.UNIT LAY ERR.]
Total of 7 or more MELSECNET, MELSECNET/B
local station data link module (A1SJ71AP23Q,
A1SJ71AR23Q, A1SJ71AT23BQ), A/QnA
intelligent communication module (A1SD51,
AD51(H)(-S3)), A/QnA JEMANET(JPCN-1)
master module (A1SJ71J92-S3, AJ71J92-S3),
A/QnA external failure diagnostics module
(AD51FD-S3), and A/QnA paging interface
module (A1SD21-S1) have been installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the total number of MELSECNET,
MELSECNET/B local station data link
modules, A/QnA intelligent communication
modules, A/QnA JEMANET(JPCN-1) master
modules, A/QnA external failure diagnostics
modules, and A/QnA paging interface
modules in the system to six or less.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU