Appendix 1 Error Codes
Appendix 1.4 List of error codes (2000 to 2999)
2103
[SP.UNIT LAY ERR.]
Two or more QI60/A1SI61/AI61(-S1) modules
are mounted in a single CPU system.
Two or more QI60/A1SI61/AI61(-S1) modules
are set to the same control CPU in a multiple
CPU system.
Two or more A1SI61/AI61(-S1) modules are
loaded in a multiple CPU system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount only one QI60/A1SI61/AI61(-S1)
module in the single CPU system.
Mount only one A1SI61/AI61(-S1) module
in the single CPU system, and set an
interrupt pointer to the QI60.
Control only one QI60/A1SI61/AI61(-S1)
module by the control CPU module in the
multiple CPU system.
Mount only one A1SI61/AI61(-S1) module
in the multiple CPU system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnU
[SP.UNIT LAY ERR.]
Two or more QI60, A1SI61 interrupt modules have
been mounted.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of QI60 and A1SI61
modules to one each.
Qn(H)
QnPRH
[SP.UNIT LAY ERR.]
Two or more QI60 modules are mounted.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount only one QI60 module. Q00J/Q00/Q01
[SP.UNIT LAY ERR.]
Two or more QI60 modules where interrupt pointer
setting has not been made are mounted.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount only one QI60 module.
Set an interrupt pointer to the second QI60
module and later.
Q00J/Q00/Q01
QnU
[SP.UNIT LAY ERR.]
An interrupt pointer set in built-in I/O function
setting parameter and the interrupt pointer for
the A1SI61 are overlapping.
Two or more A1SI61 modules are mounted.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Set interrupt pointers so that they do not
overlap.
Mount only one A1SI61 module.
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU