334
2106
[SP.UNIT LAY ERR.]
Two or more MELSECNET/H and CC-Link IE
Controller Network modules in total are
mounted in the entire system.
Two or more Ethernet modules are mounted in
the entire system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount either MELSECNET/H module or
CC-Link IE Controller Network module in
the entire system.
Mount only one Ethernet module in the
entire system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00UJCPU
[SP.UNIT LAY ERR.]
Two or more MELSECNET/H and CC-Link IE
Controller Network modules in total are
mounted in the entire system.
Two or more Ethernet modules are mounted in
the entire system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount either MELSECNET/H module or
CC-Link IE Controller Network module in
the entire system.
Mount only one Ethernet module in the
entire system.
Q00UCPU
Q01UCPU
[SP.UNIT LAY ERR.]
Three or more MELSECNET/H and CC-Link IE
Controller Network modules in total are
mounted in the entire system.
Three or more Ethernet interface modules are
mounted in the entire system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of MELSECNET/H and
CC-Link IE Controller Network modules to
two or less in the entire system.
Reduce the number of Ethernet modules to
two or less in the entire system.
Q02UCPU
[SP.UNIT LAY ERR.]
Five or more MELSECNET/H and CC-Link IE
Controller Network modules in total are
mounted in the entire system.
Five or more Ethernet interface modules are
mounted in the entire system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of MELSECNET/H and
CC-Link IE Controller Network modules to
four or less in the entire system.
Reduce the number of Ethernet modules to
four or less in the entire system.
QnU
[SP.UNIT LAY ERR.]
Three or more CC-Link IE Controller Network
modules are mounted in the entire system.
Five or more MELSECNET/H and CC-Link IE
Controller Network modules in total are
mounted in the entire system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of CC-Link IE
Controller Network modules to two or less
in the entire system.
Reduce the number of MELSECNET/H and
CC-Link IE Controller Network modules to
four or less in the entire system.
Qn(H)
QnPH
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents