335
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.4 List of error codes (2000 to 2999)
2106
[SP.UNIT LAY ERR.]
Five or more MELSECNET/H modules have
been installed.
Five or more Ethernet interface modules have
been installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of MELSECNET/H
modules to four or less.
Reduce the number of Ethernet modules to
four or less.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
[SP.UNIT LAY ERR.]
Two or more MELSECNET/H modules were
installed.
Two or more Ethernet modules were installed.
Three or more CC-Link modules were installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount only one MELSECNET/H module.
Mount only one Ethernet module.
Reduce the number of CC-Link modules to
two or less.
Q00J/Q00/Q01
[SP.UNIT LAY ERR.]
The same network number or same station
number is duplicated in the MELSECNET/H
network system.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Check the network number and station
number.
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
[SP.UNIT LAY ERR.]
Two or more Ethernet modules were installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Mount only one Ethernet module.
L02SCPU
L02SCPU-P
L02CPU
L02CPU-P
[SP.UNIT LAY ERR.]
Three or more Ethernet modules were installed.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reduce the number of Ethernet modules to
two or less.
L06CPU
L06CPU-P
L26CPU
L26CPU-P
L26CPU-BT
L26CPU-PBT
2107
[SP.UNIT LAY ERR.]
The start X/Y configured in the I/O Assignment tab
of "PLC Parameter" is overlapped with that for
another module.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Configure the I/O assignment setting of the
PLC parameter again so that it is consistent
with the actual status of the intelligent
function modules, special function modules,
and I/O modules.
RUN
: Off
ERR.:Flashing
CPU Status:Stop
QCPU
[SP.UNIT LAY ERR.]
The start X/Y configured in the I/O Assignment tab
of "PLC Parameter" is overlapped with that for
another module.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Configure the start X/Y again in the I/O
Assignment tab of "PLC Parameter"
according to the intelligent function module
and I/O modules connected.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU