[SP.UNIT LAY ERR.]
The A1SJ71LP21, A1SJ71LR21, A1SJ71BR11,
A1SJ71AP21, A1SJ71AR21, or A1SJ71AT21B
network module dedicated for the A2USCPU is
used.
The A1SJ71QLP21, A1SJ71QLP21S,
A1SJ71QLR21, or A1SJ71QBR11 network
module dedicated for the Q2ASCPU is used.
The AJ71LP21, AJ71LP21G, AJ71BR11,
AJ71AP21, AJ71AR21, or AJ71AT21B network
module dedicated for the A2UCPU is used.
The AJ71QLP21, AJ71QLP21S, AJ71QLP21G
or AJ71QBR11 network module dedicated for
the Q2ACPU is used.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Replace the network module for the
A2USCPU, Q2ASCPU, A2UCPU, or
Q2ACPU with the MELSECNET/H module.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnU
[SP.UNIT LAY ERR.]
The A1SJ71LP21, A1SJ71LR21, A1SJ71BR11,
A1SJ71AP21, A1SJ71AR21, or A1SJ71AT21B
network module dedicated for the A2USCPU is
used.
The A1SJ71QLP21, A1SJ71QLP21S,
A1SJ71QLR21, or A1SJ71QBR11 network
module dedicated for the Q2ASCPU is used.
Collateral information
Common information: Module No. (Slot No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Disconnect the corresponding module. Use
the CC-Link IE Field Network master/local
module.
LCPU
2110
[SP. UNIT ERROR]
The location designated by the FROM/TO
instruction set is not the intelligent function
module/special function module.
The module that does not include buffer
memory has been specified by the FROM/TO
instruction.
The intelligent function module/special function
module, Network module being accessed is
faulty.
Station not loaded was specified using the
instruction whose target was the CPU share
memory.
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
Read the individual information of the error
using the programming tool to identify the
numeric value (program error location).
Correct the FROM/TO instruction
corresponding to the value as necessary.
The cause is a hardware fault of the
intelligent function module/special function
module in the access destination. Please
consult your local Mitsubishi
representative.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
[SP. UNIT ERROR]
A module other than intelligent function modules
is specified with the FROM/TO instruction.
The module specified with the FROM/TO
instruction does not have the buffer memory.
The intelligent function module being accessed
is faulty.
Collateral information
Common information: Module No. (Slot No.)
Individual information: Program error location
Diagnostic timing
When instruction executed
Read the individual information of the error
using the programming tool to identify the
numeric value (program error location).
Correct the FROM/TO instruction
corresponding to the value as necessary.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.