376
4004
[INSTRCT. CODE ERR]
The device which cannot be used by the dedicated
instruction specified by the program is specified.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN/When
instruction executed
• When instruction executed (SFC program)
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
4010
[MISSING END INS.]
There is no END (FEND) instruction in the
program.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
4020
[CAN'T SET(P)]
• The total points of the pointers used in the
program exceeded 4096 points.
• The total points of the local pointers used in the
program exceeded the start number of the
common pointer.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
LCPU
[CAN'T SET(P)]
• The total points of the pointers used in the
program exceeded 512 points.
• The total points of the local pointers used in the
program exceeded the start number of the
common pointer.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Q00UJ/Q00U/Q01
U
4021
[CAN'T SET(P)]
The same pointer number is assigned to common
pointers or local pointers assigned to each file.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Read common information of the error using
th
e programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
4030
[CAN'T SET(I)]
The allocation pointer Nos. assigned by files
overlap.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU