387
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.6 List of error codes (4000 to 4999)
4430
[SFC EXE. ERROR]
The SFC program cannot be executed.
The data of the block data setting is illegal.
The SFC data device of the block data setting is
beyond the device setting range set in "PLC
Parameter".
Collateral information
Common information: File name/Drive name
Individual information: -
Diagnostic timing
At power-on/At reset/STOP RUN/When SFC
program is executed
Write the program to the CPU module
again using the programming tool.
After correcting the setting of the SFC data
device, write it to the CPU module.
Correct the device setting range in "PLC
Parameter", and write it to the CPU
module.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
LCPU
4431
[SFC EXE. ERROR]
The SFC program cannot be executed.
The block parameter setting is abnormal.
Collateral information
Common information: File name/Drive name
Individual information: -
Diagnostic timing
At power-on/At reset/STOP RUN
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
LCPU
4432
[SFC EXE. ERROR]
The SFC program cannot be executed.
The structure of the SFC program is illegal.
Collateral information
Common information: File name/Drive name
Individual information: -
Diagnostic timing
At power-on/At reset/STOP RUN
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
LCPU
4500
[SFCP. FORMAT ERR.]
The numbers of BLOCK and BEND instructions in
an SFC program are not equal.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
•STOP RUN
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
4501
[SFCP. FORMAT ERR.]
The configuration of the STEP* to TRAN* to TSET
to SEND instructions in the SFC program is
incorrect.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic ti
ming
•STOP RUN
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
4502
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
STEPI* instruction does not exist in the block of
the SFC program.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
At power-on/At reset/STOP RUN
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents