388
4503
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
The step specified in the TSET instruction does
not exist.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
•STOP RUN
Write the program to the CPU module
again using the programming tool.
Read common information of the error
using the programming tool to identify the
numeric value (program error location).
Check the error step corresponding to the
value, and correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
The step specified in the TSET instruction does
not exist.
In jump transition, the host step number was
specified as the destination step number.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When SFC program is executed
Q00J/Q00/Q01
QnU
LCPU
4504
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
The step specified in the TAND instruction does
not exist.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When SFC program is executed
Write the program to the CPU module again
using the programming tool.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
4505
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
In the operation output of a step, the SET
Sn/BLmSn or RST Sn/BLmSn instruction was
specified for the host step.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
LCPU
4506
[SFCP. FORMAT ERR.]
The structure of the SFC program is illegal.
In a reset step, the host step number was
specified as the destination step.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN:
Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnU
LCPU
4600
[SFCP. OPE. ERROR]
The SFC program contains data that cannot be
processed.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
4601
[SFCP. OPE. ERROR]
Exceeds device range that can be designated by
the SFC program.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU