389
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.6 List of error codes (4000 to 4999)
4602
[SFCP. OPE. ERROR]
The START instruction in an SFC program is
preceded by an END instruction.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
4610
[SFCP. EXE. ERROR]
The active step information at presumptive start of
the SFC program is incorrect.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
•STOP RUN
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
The program is automatically subjected to an
initial start.
RUN: On
ERR.:On
CPU Status:Continue
Qn(H)
QnPH
QnPRH
4611
[SFCP. EXE. ERROR]
Key-switch was reset during RUN when
presumptive start was designated for SFC
program.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
•STOP RUN
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
The program is automatically subjected to an
initial start.
RUN: On
ERR.:On
CPU Status:Continue
Qn(H)
QnPH
QnPRH
4620
[BLOCK EXE. ERROR]
Startup was executed at a block in the SFC
program that was already started up.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
4621
[BLOCK EXE. ERROR]
Startup was attempted at a block that does not
exist in the SFC program.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error
using the programming tool to identify the
numeric value (program error location).
Check the error step corresponding to the
value, and correct it as necessary.
Turn on SM321 if it is off.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
4630
[STEP EXE. ERROR]
The step specified in the SFC program is already
activated.
Col
lateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
4631
[STEP EXE. ERROR]
Startup was attempted at the step that does not
exist in the SFC program. Or, the step that does
not exist in the SFC program was specified for
end.
Forced transition was executed based on the
transition condition that does not exit in the SFC
program. Or, the transition condition for forced
transition that does not exit in the SFC program
was canceled.
Collateral information
Common information: Program error location
Individual information: -
Diagnostic timing
When instruction executed
Read common information of the error
using the programming tool to identify the
numeric value (program error location).
Check the error step corresponding to the
value, and correct it as necessary.
Turn on SM321 if it is off.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents