(8) Debugging
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM800 Trace preparation
OFF: Not ready
ON: Ready
Turns on when the trace preparation is
completed.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM801 Trace start
OFF: Suspend
ON: Start
When this relay is turned on while the
CPU module is set to RUN, a trace will
be started.
When this relay is turned off, a trace is
stopped. (The related special relays
will all turn off)
S (Status
change)/U
M9047
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM802
Trace execution in
progress
OFF: Suspend
ON: Start
This relay is on while a trace is being
executed.
S (Status
change)
M9046
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM803 Trace trigger OFF ON:Start
This relay turns on when the specified
trigger condition is met.
This relay is turned on to meet the
trigger condition.
S (Status
change)/U
New
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM804 After trace trigger
OFF: Not after trigger
ON: After trigger
Turns on after trace is triggered.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM805 Trace completed
OFF: Not completed
ON: Completed
This relay turns on when a trace is
completed.
S (Status
change)
M9043
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM826 Trace error
OFF: Normal
ON: Errors
This relay turns on if an error occurs
during trace.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
*1
LCPU
SM829
Forced registration
specification of
trace setting
ON: Forced
registration
enabled
OFF: Forced
registration
disabled
When this relay is turned on and a
sampling trace setting is registered using
a programming tool, the sampling trace
setting can be registered with the CPU
module even when the trigger condition
has been met.
UNew
QnU
*1
LCPU
SM830
Real-time monitor
in progress
ON : Being executed
OFF : Not executed
Turns on during real-time monitor in
progress
S (Status
change)
New
LCPU
*2
SM841 Auto logging
OFF: Not executed
ON: Being executed
This relay is on while the auto logging is
being executed.
This relay turns off when auto logging is
completed and the SD memory card lock
switch is pressed and held for 1 second
or longer to stop access to the SD
memory card.
S (Status
change)
New
QnUDV
This relay is on while auto logging is
being executed.
This relay turns off when auto logging is
completed and the SD memory card lock
switch is slid toward the module top to
stop access to the SD memory card.
LCPU

Table of Contents