478
To use the converted special relay in the High Performance model QCPU, Process CPU, Universal model QCPU, or LCPU,
check "Use special relay/special register from SM/SD1000" under "A-PLC Compatibility Setting".
Project window [Parameter] [PLC Parameter] [PLC System]
Note that the processing time will increase when the converted special relay is used.
[How to read the Special Relay for Modification column]
If the special relay number for QCPU or LCPU is provided, correct the program using it.
means that the converted special relay can be used.
means that the special relay cannot be used in QCPU or LCPU.
ACPU
Special
Relay
Special
Relay after
Conversion
Special
Relay after
Modification
Name Meaning Details
Corresponding
CPU
M9000 SM1000 Fuse blown
OFF: Normal
ON: Module with blown
fuse
This relay turns on if there is at least one
output module whose fuse has blown.
This relay remains on even after the
system returns to normal.
Output modules on remote I/O stations
are also checked.
Qn(H)
QnPH
QnU
*1
LCPU
*4
M9002 SM1002
I/O module
verify error
OFF: Normal
ON: Error
This relay turns on if the status of the I/O
module differs from that registered at
power-on.
This relay remains on even after the
system returns to normal.
I/O modules on remote I/O stations are
also checked.
This relay is reset only when SD1116 to
SD1123 are reset.
Qn(H)
QnPH
QnU
*1
LCPU
M9005 SM1005
AC DOWN
detection
OFF: AC DOWN not
detected
ON: AC DOWN detected
This relay turns on if a momentary power
failure within 20ms occurs during use of
an AC power supply module.
This relay is reset when the CPU module
is powered off and then on.
Qn(H)
QnPH
QnU
*1
This relay turns on if a momentary power
failure within 10ms occurs when using an
AC power supply module.
This relay is reset when the CPU module
is powered off and then on.
LCPU
This relay turns on if a momentary power
failure within 10ms occurs during use of
a DC power supply module.
This relay is reset when the CPU module
is powered off and then on.
Qn(H)
QnPH
QnU
*1
LCPU
M9006 SM1006 Battery low
OFF: Normal
ON: Battery low
This relay turns on when the battery
voltage drops to or below the specified.
It turns off when the battery voltage
returns to normal.
Qn(H)
QnPH
QnU
*1
LCPU
M9007 SM1007 Battery low latch
OFF: Normal
ON: Battery low
This relay turns on when the battery
voltage drops to or below the specified.
This relay remains on even after the
battery voltage returns to normal.
Qn(H)
QnPH
QnU
*1
LCPU
M9008 SM1008 SM1
Self-diagnostic
error
OFF: No error
ON: Error
This relay turns on if an error is detected by
self-diagnostics.
Qn(H)
QnPH
QnU
*1
LCPU
M9009 SM1009 SM62
Annunciator
detection
OFF: No F number
detected
ON: F number detected
This relay turns on when the OUT F or
SET F instruction is executed.
It turns off when the SD1124 value is
cleared to zero.
Qn(H)
QnPH
QnU
*1
LCPU