EasyManua.ls Logo

Mitsubishi EHST20D-YM9C - Troubleshooting by Inferior Phenomena; Cylinder Unit

Mitsubishi EHST20D-YM9C
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
69
10-5. Troubleshooting by inferior phenomena
No. Fault symptom Possible cause Explanation - Solution
1 Main remote controller
display is blank.
1. Thereisnopowersupplytomainremote
controller.
1. CheckLED2onFTC.(See"6.WIRINGDIAGRAM".)
(i) When LED2 is lit.
Checkfordamageorcontactfailureofthemainremotecontrollerwiring.
(ii)WhenLED2isblinking.
RefertoNo.5below.
(iii) When LED2 is not lit.
RefertoNo.4below.
2. Powerissuppliedtomainremote
controller,however,thedisplayonthe
main remote controller does not appear.
2. Checkthefollowing:
•DisconnectionbetweenthemainremotecontrollercableandtheFTCcontrol
board
•Failureofthemainremotecontrollerif“PleaseWait”isnotdisplayed.
•RefertoNo.2belowif“PleaseWait”isdisplayed.
2 “Please Wait” remains
displayed on the main
remote controller.
1. "PleaseWait"isdisplayedforupto6
minutes.
1. Normal operation
2. Communicationfailurebetweenthemain
remote controller and FTC.
2, 3.
Main remote controller start up checks/procedure.
(i)If“0%”or“50–99%”isdisplayedbelow"PleaseWait"thereisa
communicationerrorbetweenthemainremotecontrollerandtheFTCcontrol
board.
•Checkwiringconnectionsonthemainremotecontroller.
•ReplacethemainremotecontrollerortheFTCcontrolboard.
(ii)If“1–49%”isdisplayedthereisacommunicationerrorbetweentheoutdoor
unit's and FTC's control boards.
•CheckthewiringconnectionsontheoutdoorunitcontrolboardandtheFTC
control board.
(EnsureS1 and S2arenotcross-wiredandS3 is securelywiredwithno
damage.(See"7.FIELDWIRING".)
•Replacetheoutdoorunit'sand/ortheFTC'scontrolboards.
3. CommunicationfailurebetweenFTCand
outdoor unit.
3 The main screen
appearswithapress
of the “ON” button, but
disappears in a second.
The main remote controller operations do
notworkforawhileafterthesettingsare
changedintheservicemenu.Thisisbecause
thesystemtakestimetoapplythechanges.
Normal operation
Theindoorunitisapplyingupdatedsettingsmadeintheservicemenu.Normal
operationwillstartshortly.
4 LED2 on FTC is off.
(See"6.WIRING
DIAGRAM".)
WhenLED1onFTCisalsooff.(See"6.
WIRINGDIAGRAM".)
<FTCpoweredviaoutdoorunit.>
1. The outdoor unit is not supplied at the
ratedvoltage.
1. CheckthevoltageacrosstheterminalsLandNorL3andNontheoutdoor
powerboard.(See"7.FIELDWIRING".)
•Whenthevoltageisnot220to240VAC,checkwiringoftheoutdoorunitand
of the breaker.
•Whenthevoltageisat220to240VAC,goto“2.”below.
2. Defective outdoor controller circuit board 2. CheckthevoltageacrosstheoutdoorunitterminalsS1andS2.(See"7.FIELD
WIRING".)
•Whenthevoltageisnot220to240VAC,checkthefuseontheoutdoor
controlboardandcheckforfaultywiring.
•Whenthevoltageis220to240VAC,goto“3.”below.
3. FTCisnotsuppliedwith220to240V
AC.
3. CheckthevoltageacrosstheindoorunitterminalsS1andS2.(See"7.FIELD
WIRING".)
•Whenthevoltageisnot220to240VAC,checkFTC-outdoorunitwiringfor
faults.
•Whenthevoltageis220to240VAC,goto“4.”below.
4. FTC failure 4. Check the FTC control board.
•CheckthefuseonFTCcontrolboard.
•Checkforfaultywiring.
•Ifnoproblemfoundwiththewiring,theFTCcontrolboardisfaulty.
5. Faultyconnectorwiring 5. Checktheconnectorwiring.
•Whentheconnectorsarewiredincorrectly,re-wiretheconnectorsreferringto
below.(See"7.FIELDWIRING".)
S1
S2
S3
L
N
CN01
CN01
BLACK
YELLOW
YELLOW
BLACK
Initialsettings
(Power
supplied by
outdoor unit)
Cylinder unit
control board
White
OCH570C

Table of Contents

Related product manuals