74
No. Fault symptom Possible cause Explanation - Solution
34 Theenergymonitorval-
ue seems not correct.
Note:
There could be some
discrepanciesbetweenthe
actual and the calculated
values.
If you seek for accuracy,
please make sure to
connectpowermeter(s)
and heat meter to FTC
board.
Both should be
locally supplied.
1.Incorrectsettingoftheenergymonitor 1.Checkthesettingbyfollowingtheprocedurebelow.
(1)CheckiftheDIPswitchissetasthetablebelow.
Consumedelectricenergy
SW3-4
Electricenergymeter
(Local supply)
OFF Without
ON With
(2)Inthecaseexternalelectricenergymeterand/orheatmeterisnotused,
checkifthesettingforelectricheaterandwaterpump(s)inputiscorrectby
referringto<Energymonitorsetting>in"9-4.Servicemenu".
(3)Inthecaseexternalelectricenergymeterand/orheatmeterisused,check
iftheunitofoutputpulseonexternalmetermatcheswiththeonesetatthe
mainremotecontrollerbyreferringto<Energymonitorsetting>in"9-4.Ser-
vicemenu".
2.Non-connectabletypeofexternalmeter(local
supply) is connected.
2.Checkiftheexternalmeter(localsupply)isconnectabletypebyreferringto
<Energymonitorsetting>"in"9-4.Servicemenu".
3.Externalmeter(localsupply)failure 3.CheckifsignalissenttoIN8toIN10properly.(Refertosection6.WIRING
DIAGRAM)
Replacetheexternalheatmeterifdefective.
4. FTC board failure 4. Check the FTC control board.
•Checkforfaultywiring.
•Ifnoproblemfoundwiththewiring,theFTCcontrolboardisfaulty.Replace
the board.
35 Heat pump is forced to
turn ON and OFF.
Smartgridreadyinput(IN11andIN12)isused,
andswitch-onandoffcommandsareinput.
Normal operation no action necessary.
Deliveredheatenergy
SW3-8
Heat meter
(Local supply)
OFF Without
ON With
Annual Maintenance
Itisessentialthatthecylinderunitisservicedatleastonceayearbyaqualiedindividual.AnysparepartsrequiredshouldbepurchasedfromMitsubishiElectric.
NEVERbypasssafetydevicesoroperatetheunitwithoutthembeingfullyoperational.
<Annual maintenance points>
UsetheAnnualMaintenanceLogBookasaguidetocarryingoutthenecessarychecksonthecylinderunitandoutdoorunit.