PRECAUTIONS FOR MAINTENANCE AND INSPECTION
5.1.6 Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced
performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Use the life check function as a guidance of parts replacement.
 Estimated lifespan for when the yearly average ambient temperature is 35°C.
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
 Output current: 80% of the inverter rating
 The estimated lifespan is only a guide. To maintain the waterproof and dustproof performances of the inverter, daily and periodic inspections are
recommended.
NOTE
For parts replacement, contact the nearest Mitsubishi FA center.
Displaying the life of the inverter parts
The inverter diagnoses the main circuit capacitor, control circuit capacitor, cooling fan, internal fan, and inrush current limit
circuit by itself and estimates their lives.
The self-diagnostic warning is output when the life span of each part is near its end. It gives an indication of replacement time.
The life warning output can be used as a guideline for life judgment.
NOTE
Refer to the FR-A800 Instruction Manual (Detailed) to perform the life check of the inverter parts.
Part name Estimated lifespan Description
Cooling fan, internal fan 10 years Replace (as required)
Main circuit smoothing capacitor 10 years
 Replace (as required)
On-board smoothing capacitor 10 years
 Replace the board (as required)
Relays As required
Gasket 2 years
 Replace (as required)
Parts Judgment level
Main circuit capacitor 85% of the initial capacity
Control circuit capacitor Estimated remaining life 10%
Inrush current limit circuit Estimated remaining life 10% (Power ON: 100,000 times left)
Cooling fan Not more than the specified speed