Safety Instructions
3
 IPX5 refers to protection of the inverter functions against water jets from
any direction when about 12.5-liter water
 is injected from a nozzle with
an inside diameter of 6.3 mm from the distance of about 3 m for at least 3
minutes.
 IP5X refers to protection of the inverter functions and maintenance of
safety when the inverter is put into a stirring device containing dust of 75
µm or smaller in diameter, stirred for 8 hours, and then removed from the
device.
 Water here refers to fresh water at room temperature (5 to 35°C).
 Indoor here refers to the environments that are not affected by climate
conditions.
CAUTION
Emergency stop
 A safety backup such as an emergency brake must be 
provided for devices or equipment in a system to prevent 
hazardous conditions in case of failure of this product or an 
external device controlling this product.
 If the breaker installed on the input side of this product 
trips, check for wiring faults (short circuits etc.) and damage 
to internal parts of this product. The cause of the trip must 
be identified and removed before turning ON the power of 
the breaker.
 When a protective function activates, take an appropriate 
corrective action, then reset the inverter, and resume the 
operation.
Maintenance, inspection and parts replacement
 Do not carry out a megger (insulation resistance) test on the 
control circuit of the inverter. It will cause failure.
Disposal
 The inverter must be treated as industrial waste.
CAUTION
Waterproof and dustproof performances
 The inverter is rated with an IPX5
 waterproof rating and an 
IP5X
 dustproof rating when the operation panel (FR-DU08-
01), the front cover, the wiring cover, and the cable glands 
are securely fixed with screws.
 The items enclosed with the inverter such as the Instruction 
Manual or CD are not rated with the IPX5 waterproof or IP5X 
dustproof ratings.
 Although the inverter is rated with the IPX5 waterproof and 
IP5X dustproof ratings, it is not intended for use in water. 
Also, the ratings do not guarantee protection of the inverter 
from needless submersion in water or being washed under 
strong running water such as a shower.
 Do not pour or apply the following liquids over the inverter: 
water containing soap, detergent, or bath additives; sea 
water; swimming pool water; warm water; boiling water; etc.
 The inverter is intended for indoor
 installation and not for 
outdoor installation. Avoid places where the inverter is 
subjected to direct sunlight, rain, sleet, snow, or freezing 
temperatures. 
 If the operation panel (FR-DU08-01) is not installed, if the 
screws of the operation panel are not tightened, or if the 
operation panel is damaged or deformed, the IPX5 
waterproof performance and the IP5X dustproof 
performance are impaired. If any abnormalities are found on 
the operation panel, ask for an inspection and repair.
 If the screws of the front cover or the wiring cover are not 
tightened, if any foreign matter (hair, sand grain, fiber, etc.) 
is stuck between the inverter and the gasket, if the gasket is 
damaged, or if the front cover or the wiring cover is 
damaged or deformed, the IPX5 waterproof performance 
and the IP5X dustproof performance are impaired. If any 
abnormalities are found on the front cover, wiring cover, or 
the gasket of the inverter, ask for an inspection and repair.
 Cable glands are important components to maintain the 
waterproof and dustproof performances. Be sure to use 
cable glands of the recommended size and shape or 
equivalent. The standard protective bushes cannot 
sufficiently maintain the IPX5 waterproof performance and 
the IP5X dustproof performance.
 If a cable gland is damaged or deformed, the IPX5 
waterproof performance and the IP5X dustproof 
performance are impaired. If any abnormalities are found on 
the cable glands, ask the manufacturer of the cable glands 
for an inspection and repair.
 To maintain the waterproof and dustproof performances of 
the inverter, daily and periodic inspections are 
recommended regardless of the presence or absence of 
abnormalities.
General instruction
 Many of the diagrams and drawings in the Instruction 
Manual show the product without a cover or partially open 
for explanation. Never operate the product in this manner. 
The cover must be always reinstalled and the instruction in 
the Instruction Manual must be followed when operating the 
product. For more details on the PM motor, refer to the 
Instruction Manual of the PM motor.
Application of caution labels
Caution labels are used to ensure safety during use of Mitsubishi 
Electric inverters.
Apply the following labels to the inverter if the "retry function" and/
or "automatic restart after instantaneous power failure" have been 
enabled.
 For the retry function
 For automatic restart after instantaneous power failure
Application of motor control labels
Apply the following labels to the inverter to avoid connecting 
motors not intended for a particular motor control setting.
CAUTION
Retry Function Has
Been Selected 
Stay away from the motor and machine.
They will start suddenly (after given
time has elapsed) when alarm occurs.
CAUTION
Automatic Restart after
Instantaneous Power
Failure Has Been Selected
Stay away from the motor and machine.
They will start suddenly (after reset 
time has elapsed) when
instantaneous power failure occurs.
Induction motor setting
The inverter is set for the induction 
motor control.
IM LED is ON during induction motor 
control.
Do not drive a PM motor.
PM motor control setting
The inverter is set for the PM motor 
control.
PM LED is ON during PM motor control.
Do not drive an induction motor.