40
Before operation
3.3 Before operation
3.3.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. (For details of parameters,
Refer to Chapter 4 of the Instruction Manual (Applied)).
POINT
Only simple mode parameters are displayed by the initial setting of
Pr. 160 Extended function display selection
. Set
Pr.
160 Extended function display selection
as required. (
Refer to page 37
for parameter change)
Pr. 160 Description
9999
(initial value)
Parameters classified as simple mode can be displayed.
0
Both the parameters classified as simple mode and the parameters
classified as extended mode can be displayed.
Parameter
Number
Name Unit
Initial
Value
Range Application
Reference
Page
0 Torque boost 0.1%
6%/4%/3/
2%
0 to 30%
Set when you want to increase a
starting torque under V/F control,
or when the motor with a load will
not rotate, resulting in an alarm
[OL] and a trip [OC1].
Initial values differ according to the
inverter capacity. (0.75K or less/
1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
44
1 Maximum frequency 0.01Hz 120Hz 0 to 120Hz
Set when the maximum output
frequency need to be limited.
45
2 Minimum frequency 0.01Hz 0Hz 0 to 120Hz
Set when the minimum output
frequency need to be limited.
3 Base frequency 0.01Hz 60Hz 0 to 400Hz
Set when the rated motor
frequency is 50Hz.
Check the motor rating plate.
43
4
Multi-speed setting
(high speed)
0.01Hz 60Hz 0 to 400Hz
Set when changing the preset
speed in the parameter with a
terminal.
64
5
Multi-speed setting
(middle speed)
0.01Hz 30Hz 0 to 400Hz
6
Multi-speed setting (low
speed)
0.01Hz 10Hz 0 to 400Hz
7 Acceleration time 0.1s 5s/10s/15s 0 to 3600s
Acceleration/deceleration time can
be set.
Initial values differ according to the
inverter capacity. (3.7K or less/
5.5K, 7.5K/11K, 15K)
46
8 Deceleration time 0.1s 5s/10s/15s 0 to 3600s
9
Electronic thermal O/L
relay
0.01A
Rated
inverter
current
0 to 500A
The inverter protects the motor
from overheat.
Set the rated motor current.
41
79
Operation mode
selection
10
0, 1, 2, 3, 4, 6,
7
Select the start command location
and frequency setting location.
47
125
Terminal 2 frequency
setting gain frequency
0.01Hz 60Hz 0 to 400Hz
Frequency for the maximum value
of the potentiometer (5V initial
value) can be changed.
68
126
Terminal 4 frequency
setting gain frequency
0.01Hz 60Hz 0 to 400Hz
Frequency for the maximum
current input (20mA initial value)
can be changed.
71
160
Extended function
display selection
1 9999 0, 9999
Parameter which can be read from
the operation panel and parameter
unit can be restricted.
74