DRIVE THE MOTOR
3
Before operation
3.3.7 Selection of the start command and frequency command locations (Pr. 79)
Select the start command location and frequency command location.
POINT
Setting value "1" to "4" can be changed in the easy setting mode. (Refer to page 34)
Parameter
Number
Name
Initial
Value
Setting
Range
Description
LED
Indication
:Off
:On
79
Operation
mode selection
0
0
External/PU switchover mode
Press to switch between the PU and External operation
mode.
(Refer to page 54)
At power on, the inverter is in the External operation mode.
External
operation mode
PU operation
mode
1 Fixed to PU operation mode
2
Fixed to External operation mode
Operation can be performed by switching between the external
and NET operation mode.
External
operation mode
NET operation
mode
3
External/PU combined operation mode 1
Frequency Command Start Command
Operation panel and PU (FR-
PU04/FR-PU07) setting or
external signal input (multi-
speed setting, across terminals
4-5 (valid when AU signal turns
ON)). ∗1
External signal input
(terminal STF, STR)
4
External/PU combined operation mode 2
Frequency Command Start Command
External signal input
(terminal 2, 4, JOG, multi-speed
selection, etc.)
Input using of the
operation panel and and
of the PU(FR-PU04/FR-
PU07)
6
Switchover mode
Switchover between PU operation, External operation, and NET
operation can be done while keeping the same operation status.
PU operation
mode
External
operation mode
NET operation
mode
7
External operation mode (PU operation interlock)
X12 signal ON ∗2
Can be shifted to PU operation mode (output stop during
external operation)
X12 signal OFF ∗2
Operation mode can not be switched to the PU operation mode.
PU operation
mode
External
operation mode
∗1 The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU)
> digital input from the operation panel".
∗2 For the terminal used for the X12 signal (PU operation interlock signal) input, set "12" in Pr. 178 to Pr. 182 (input terminal function selection) to assign functions.
Refer to Chapter 4 of the Instruction Manual (Applied) for Pr. 178 to Pr. 182.
When the X 12 signal has not been assigned, the function of the MRS signal switches from MRS (output stop) to the PU operation interlock signal.