EasyManua.ls Logo

Mitsubishi FR-D740-1.5K - Page 70

Mitsubishi FR-D740-1.5K
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
61
DRIVE THE MOTOR
3
Start/stop from the operation panel (PU operation)
8. Change the Pr. 79 setting to "4".
(Refer to page 34 for change of the setting.)
[PU] display and [EXT] display are lit.
9. Start
Check that the terminal 4 input selection signal
(AU) is ON.
Turn ON .
[RUN] flickers fast because the frequency
command is not given.
10.Acceleration constant speed
Perform 20mA input.
The frequency value on the indication
increases according to Pr. 7 Acceleration time
until " "(60.00Hz) is displayed.
[RUN] display is lit during forward rotation
operation and flickers slowly during reverse
rotation operation.
11.Deceleration
Perform 4mA input.
The frequency value on the indication decreases
according to
Pr. 8 Deceleration time
and displays
" " (0.00Hz) when the motor is stopped.
[RUN] flickers fast.
12.Stop
Switch power OFF .
[RUN] turns OFF.
REMARKS
Change the frequency (60Hz) at the maximum current input (at 20mA, initial value)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 71)
Change the frequency (0Hz) at the minimum current input (at 4mA, initial value)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. ( Refer to Chapter 4 of the
Instruction Manual (Applied).)
Operation Display
Flickering
Current signal
source
(4 to 20mADC)
Current signal
source
(4 to 20mADC)
Flickering
Stop

Table of Contents

Related product manuals