79
DRIVE THE MOTOR
3
Parameter list
Parameter List
Change of DU/PU monitor descriptions
Cumulative monitor clear
52
DU/PU main
display data
selection
10
0, 5, 8 to
12, 14, 20,
23 to 25,
52 to 55,
61, 62, 64,
100
Select monitor to be displayed on the
operation panel and parameter unit and
monitor to be output to the terminal FM.
0: Output frequency (Pr.52)
1: Output frequency (Pr.54)
2: Output current (Pr.54)
3: Output voltage (Pr.54)
5: Frequency setting value
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load
factor
11: Output current peak value
12: Converter output voltage peak value
14: Output power
20: Cumulative energization time (Pr. 52)
21: Reference voltage output (Pr. 54)
23: Actual operation time (Pr. 52)
24: Motor load factor
25: Cumulative power (Pr. 52)
52: PID set point
53: PID measured value
54: PID deviation (Pr. 52)
55: I/O terminal status (Pr. 52)
61: Motor thermal load factor
62: Inverter thermal load factor
64: PTC thermistor resistance
100: Set frequency is displayed during a
stop and output frequency is
displayed during operation (Pr. 52)

54
FM terminal
function selection
11
1 to 3, 5,
8 to 12,
14, 21,
24, 52, 53,
61, 62

170
Watt-hour meter
clear
19999
0
Set "0" to clear the watt-hour meter
monitor.
×
10
Sets the maximum value for the monitoring
from communication to 9999kW.
9999
Sets the maximum value for the monitoring
from communication to 65535kW.
171
Operation hour
meter clear
1 9999 0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" does not clear.
×××
268
Monitor decimal
digits selection
19999
0 Displayed as integral value
1 Displayed in 0.1 increments.
9999 No function
563
Energization time
carrying-over
times
10
(0 to
65535)
The numbers of cumulative energization
time monitor exceeded 65535h is
displayed. (Reading only)
×××
564
Operating time
carrying-over
times
10
(0 to
65535)
The numbers of operation time monitor
exceeded 65535h is displayed.
(Reading only)
×××
891
Cumulative power
monitor digit
shifted times
19999
0 to 4
Set the number of times to shift the
cumulative power monitor digit.
Clamp the monitor value at maximum.

9999
No shift
Clear the monitor value when it exceeds
the maximum value.