83
DRIVE THE MOTOR
3
Parameter list
Parameter List
Reset selection,
disconnected PU
detection
75
Reset selection/
disconnected PU
detection/PU stop
selection
114
0 to 3
,
14 to 17
You can select the reset input acceptance,
disconnected PU (FR-PU04/FR-PU07)
connector detection function and PU stop
function.
For the initial value, reset always enabled,
without disconnected PU detection, and
with PU stop function are set.
××
Prevention of
parameter
rewrite
77
Parameter write
selection
10
0 Write is enabled only during a stop
1 Write disabled.
2
Write is enabled in any operation mode
regardless of operation status.
Prevention of
reverse rotation
of the motor
78
Reverse rotation
prevention
selection
10
0 Both forward and reverse rotations allowed
1 Reverse rotation disabled
2 Forward rotation disabled
Operation mode selection
79
Operation mode
selection
10
0 External/PU switchover mode
1 Fixed to PU operation mode
2 Fixed to External operation mode
3 External/PU combined operation mode 1
4 External/PU combined operation mode 2
6 Switchover mode
7
External operation mode (PU operation
interlock)
340
Communication
startup mode
selection
10
0 As set in Pr. 79.
∗ ∗
1
Started in Network operation mode.
10
Started in Network operation mode.
Operation mode can be changed between
the PU operation mode and Network
operation mode from the operation panel.
General-purpose magnetic
flux vector control
80
Motor capacity
0.01kW
9999
0.1 to 15kW
Applied motor capacity. (General-purpose
magnetic flux vector control)
9999 V/F control
Function
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
Copy
Parameter
Clear
All Parameter
Clear
Related
Parameter
GP
MFVC
GP
MFVC