PARAMETERS
62
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
EC
Version
Refer
To
Page:
Cust-
omer
Set-
ting
107 V/F4 (fourth frequency voltage) 0 to 1000V 0.1V 0 108
108 V/F5 (fifth frequency) 0 to 120Hz, 9999 0.01Hz 9999 108
5-point flexible V/F
characteristics
109 V/F5 (fifth frequency voltage) 0 to 1000V 0.1V 0 108
117 Station number 0 to 31 1 0 109
118 Communication speed 48, 96, 192 1 192 109
119 Stop bit length/data length
0, 1 (data length 8)
10, 11 (data length 7)
1 1 109
120 Parity check presence/absence 0, 1, 2 1 2 109
121 Number of communication retries 0 to 10, 9999 1 1 109
122 Communication check time interval 0, 0.1 to 999.8 s, 9999 0.1 s 0
9999
109
123 Waiting time setting 0 to 150ms, 9999 1ms 9999 109
Communication functions
124 CR
LF presence/absence selection 0,1,2 1 1 109
128 PID action selection
10, 11, 20, 21
(30, 31 Note 5)

10 120
129 PID proportional band 0.1 to 1000%, 9999 0.1% 100% 120
130 PID integral time 0.1 to 3600 s, 9999 0.1 s 1 s 120
131 Upper limit 0 to 100%, 9999 0.1% 9999 120
132 Lower limit 0 to 100%, 9999 0.1% 9999 120
133 PID action set point for PU operation 0 to 100% 0.01% 0% 120
PID control
134 PID differential time 0.01 to 10.00 s, 9999 0.01 s 9999 120
135
Commercial power supply-inverter
switch-over sequence output terminal
selection
0, 1 1 0 127
136 MC switch-over interlock time 0 to 100.0 s 0.1 s 1.0 s 127
137 Start waiting time 0 to 100.0 s 0.1 s 0.5 s 127
138
Commercial power supply-inverter
switch-over selection at alarm
occurrence
0, 1 1 0 127
Commercial power supply-
inverter switch-over
139
Automatic inverter-commercial power
supply switch-over frequency
0 to 60.00Hz, 9999 0.01Hz 9999 127
140
Backlash acceleration stopping
frequency (Note 2)
0 to 120Hz 0.01Hz 1.00Hz 79
141
Backlash acceleration stopping time
(Note 2)
0 to 360 s 0.1 s 0.5 s 79
142
Backlash deceleration stopping
frequency (Note 2)
0 to 120Hz 0.01Hz 1.00Hz 79
Backlash
143
Backlash deceleration stopping time
(Note 2)
0 to 360 s 0.1 s 0.5 s 79
Display
144 Speed setting switch-over
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1482
145 Parameter for option (FR-PU04)
148
Stall prevention operation level at 0V
input
0 to 150% 0.1% 120% 77
Additional functions
149
Stall prevention operation level at 10V
input
0 to 150% 0.1% 150% 77
Parameter List