EasyManua.ls Logo

Mitsubishi FR - S500 - Page 63

Mitsubishi FR - S500
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
Function (Parameter) list
2
FUNCTIONS
Parameter List
Terminal function selection
60
RL terminal
function
selection
0: RL, 1: RM, 2: RH,
3: RT, 4: AU, 5: STOP,
6: MRS, 7: OH,
8: REX, 9: JOG,
10: RES, 14: X14,
16: X16,
- - -: STR (The STR
signal can be
assigned to the STR
terminal only.)
1098
61
RM terminal
function
selection
1198
62
RH terminal
function
selection
1298
63
STR terminal
function
selection
1- - -98
64
RUN terminal
function
selection
0:RUN, 1:SU, 3:OL,
4:FU, 11:RY, 12:Y12,
13:Y13, 14:FDN,
15:FUP, 16:RL,
93:Y93, 95:Y95 98:LF,
99:ABC
(The Y93 signal can
be assigned to the
RUN terminal only.)
10100
65
A, B, C
terminal
function
selection
199100
Operation selection functions
66
Retry
selection
0: OC1 to 3, OV1 to 3,
THM, THT, BE, GF,
OHT, OLT, PE, OPT
1: OC1 to 3,
2: OV1 to 3,
3: OC1 to 3, OV1 to 3
10101
67
Number of
retries at
alarm
occurrence
0: No retry
1 to 10:
Without alarm output
during retry operation
101 to 110:
With alarm output
during retry operation
10101
68
Retry waiting
time
0.1 to 360s 0.1s 1s 101
69
Retry count
display erase
0: Cumulative count
erase
10101
Func-
tion
Para-
meter
Indica-
tion
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting

Table of Contents

Related product manuals